Generator Calculator
Running watts vs starting watts
Every motor-driven appliance — fridge, pumps, furnace blower, air conditioner — draws a brief surge when its motor starts, typically two to eight times its running draw, lasting a fraction of a second to a few seconds. Resistive loads (heaters, coffee makers, dryers, lights) have no surge: their start figure equals their run figure. A generator must satisfy both numbers: enough running watts for the steady total, and enough surge capacity for the worst moment — which, since motors rarely start in the same instant, is conventionally calculated as the running total plus the single largest (start − run) difference among the running appliances. That is the method this calculator uses.
Generators are marketed by their peak (starting) watts with the running watts lower — a “4,500-watt” portable typically runs 3,600 continuously. Compare your required figure (running total + biggest surge) against the peak rating, and your running total against the continuous rating; both must fit. Then leave headroom: sizing to 100% of a generator’s rating makes it loud, thirsty and short-lived, so the recommendation below rounds you up to a common size class with roughly 20–25% spare.
Worked example
The defaults: refrigerator (150 run / 1,200 start), lights (300), TV (150), microwave (1,000 run / 1,200 start). Running total: 150 + 300 + 150 + 1,000 = 1,600 W. Surges above running: fridge 1,050, microwave 200, others zero — the largest is the fridge’s 1,050. Required capacity: 1,600 + 1,050 = 2,650 W, so a generator in the 3,500 W class (about 2,800–3,000 running watts) covers it with sensible headroom. Add the well pump (1,000 / 2,100) and the sums jump: running 2,600 W, biggest surge now the pump’s 1,100, required 3,700 W — a 4,500–5,500 W machine. Add central air (3,500 / 7,000) and you are in whole-house standby territory, which is the honest answer for many homes: the air conditioner is the appliance that decides the generator, and a soft-start kit on the AC — which can cut its surge by half or more — is often cheaper than the bigger generator it avoids.
Fuel, runtime and the practicalities
Size interacts with fuel: a portable petrol generator at half load burns roughly 0.4–0.75 gallons an hour depending on size, so an oversized unit idling through the night on a fridge and lights wastes fuel you may not be able to replace mid-outage. Inverter generators sip fuel at low load and are far quieter — worth the premium for the common “fridge, lights, screens, furnace blower” load profile. Whatever you choose: run it outdoors only, at least 20 feet from the house with exhaust away from windows (carbon monoxide kills outage victims every year), connect through a transfer switch or interlock rather than back-feeding a dryer outlet, and never refuel a hot engine. If your real need is a CPAP, a fridge and phones, a battery power station sized in watt-hours may serve you better and silently — the watt maths above is the same, only the storage replaces the fuel.
Frequently asked questions
What size generator do I need for my house?
Add the running watts of everything you want on at once, then add the largest single starting surge. Fridge, lights, TV and microwave: 1,600 running + 1,050 fridge surge = 2,650 W required, so a 3,500 W class generator. Add a well pump and you need about 3,700 W (4,500–5,500 W class). Add central air and most homes land at 7,500 W and up, or a standby unit. “Whole house” marketing aside, the right size is the one your ticked list produces — most outage needs are smaller than people fear, and the air conditioner is usually the item that changes the answer.
Why does a fridge need 1,200 watts if it only runs at 150?
Because starting a compressor motor is not the same as running one. For a second or so, the motor draws locked-rotor current — several times its running draw — until it gets up to speed. The generator must survive that surge without its voltage collapsing, or the fridge (and everything else) stalls. This is why generator sizing uses running total + largest surge rather than a sum of nameplate watts, and why a generator that “should be big enough” on running watts alone still fails when the fridge kicks in.
What size generator will run a 3-ton central air conditioner?
A 3-ton unit typically runs around 3,500 W but can surge to roughly 7,000 W on start (older units, more). On its own that points to a generator with at least 7,000 surge watts plus whatever else runs concurrently — realistically a 9,500–12,000 W portable or a standby unit. The alternative worth pricing first is a soft-start kit for the AC, which can cut the starting surge by 50–70% and let a mid-size generator cope. Check your unit’s nameplate LRA figure for the true surge rather than relying on any table, this one included.
Is it better to buy a bigger generator than I need?
Slightly bigger, yes; much bigger, no. About 20–25% headroom over your required watts keeps the engine in its efficient, quieter mid-range and leaves room for the appliance you forgot. Double the size, though, and you pay more up front, burn more fuel at the light loads you actually run, and lug more weight — while gaining nothing you use. Diesel and standby units dislike chronic light loading even more than portables. Size from your list, add the headroom, and stop.
Can I run my whole house on a 7,500-watt generator?
Most of it, with management: 7,500 W covers refrigeration, lights, screens, a furnace blower, a well pump and a microwave in sensible combinations, and even a window air conditioner or two. What it will not do is everything at once — central air plus an electric dryer plus a water heater is 13,000 W before anything else. The workable pattern is load rotation: water heater or dryer on while the AC is off, and so on. A transfer switch with selected circuits makes that rotation a switch-flip instead of an extension-cord exercise.