Voltage Drop Calculator

In short: drop grows with current and distance and shrinks with wire size. 20 A over 100 ft on 12 AWG copper drops 7.90 V — 6.6% of 120 V, over the 3% branch-circuit guideline; 10 AWG brings it to 4.97 V.

Why distance is the silent variable

Ampacity tables — the ones that say 12 AWG carries 20 A — are about heat, and they assume ordinary short runs. Voltage drop is a separate failure mode that appears with distance: the same perfectly legal 12 AWG circuit that is fine at 25 feet is delivering barely 113 V at 100 feet under full load. Lights dim, motors strain, and a compressor's starting torque falls away. Solar installations, outbuildings, well pumps, boat shore-power leads and long workshop runs are where the drop check earns its keep — all long, all heavily loaded, all routinely wired by ampacity alone.

The formula's structure tells you the design options at a glance. Drop is linear in current and in distance — double either, double the drop — but the wire gauge works in steps: cross-sectional area doubles about every three AWG numbers, halving the drop each time. That is why the fix is usually one or two sizes up, and why the cost difference between "just legal" and "actually right" on a long run is often surprisingly small compared with the labour of pulling the cable twice.

A note on three-phase and DC

This calculator covers single-phase AC and DC, which share the round-trip formula used here (DC has no reactance, so the resistive formula is the whole story). Three-phase drop uses √3 instead of 2 as the multiplier and the line-to-line voltage — the drop comes out lower for the same power, one of three-phase's efficiencies. Large AC conductors also develop inductive reactance that adds to the drop at big sizes and low power factors; below about 2 AWG in ordinary branch work the resistive calculation on this page is the accepted approximation.

A quick field check

Calculation aside, a loaded voltage measurement tells the truth about an existing run: measure the voltage at the far end with the load switched off, then with it running at full draw. The difference is the actual drop under that load, and it should land close to this calculator's figure for the run's length and gauge. A much larger measured drop points at the connections rather than the cable — a loose terminal adds resistance exactly where it does most harm and is the usual culprit when one outlet misbehaves on an otherwise sound circuit. That check, done with a plug-in meter, is the fastest way to separate a design problem (undersized cable, this page's territory) from an installation fault.

Frequently asked questions

How do you calculate voltage drop?

For a single-phase circuit: VD = (2 x K x I x L) / CM. K is the conductor's resistivity constant — 12.9 for copper, 21.2 for aluminium, in ohm-circular-mils per foot; I is the current in amps; L is the one-way distance in feet; CM is the wire's cross-section in circular mils from the AWG table. The 2 accounts for the round trip: current travels out on one conductor and back on the other, so the run's resistance is doubled. Example: 20 A over 100 ft on 12 AWG copper (6,530 cmil): (2 x 12.9 x 20 x 100) / 6,530 = 7.90 V — 6.6% of a 120 V supply, well past the guideline.

How much voltage drop is acceptable?

The widely used guidance from the US National Electrical Code's informational notes is a maximum of 3% on a branch circuit and 5% total from service to the furthest outlet. Those are recommendations for efficiency and equipment performance rather than hard code limits, but they are the figures designs are judged by. Motors are the most sensitive loads — a motor at 10% undervoltage draws more current, runs hotter and loses torque — while modern electronics tolerate wide ranges. For 12 V systems (vehicles, solar, boats) even 3% is only 0.36 V, which is why low-voltage runs need dramatically thicker cable than intuition suggests.

How do I fix an excessive voltage drop?

The drop is proportional to current and distance and inversely proportional to conductor area, so there are three levers. Upsize the wire — each step of about three AWG sizes halves the resistance, so going from 12 to 10 AWG cuts the example above from 7.90 V to 4.97 V. Shorten the run or move the supply closer to the load. Or reduce the current on that circuit by splitting loads across two circuits. Raising the system voltage is the structural fix where it is an option: the same power at 240 V instead of 120 V halves the current and quarters the percentage drop, which is why long rural runs and EV chargers favour the higher voltage.

Why does aluminium wire drop more voltage than copper?

Aluminium is the poorer conductor: its resistivity constant K is 21.2 against copper's 12.9, so the same gauge of aluminium drops about 64% more voltage over the same run. The standard compensation is to go two AWG sizes larger in aluminium for the same drop — 10 AWG aluminium roughly matches 12 AWG copper. Aluminium's advantages are cost and weight, which is why it dominates large service and feeder cables where upsizing is cheap; copper dominates small branch wiring where the size penalty and termination care outweigh the saving.

Does voltage drop waste energy?

Yes — the dropped volts are dissipated as heat in the cable, at a rate of VD x I watts. The 7.90 V example at 20 A is losing 158 W along the run: real money over a year on a continuous load, and a cable running warm inside a wall. That energy cost is a second reason, beyond equipment performance, for the 3% guideline on heavily loaded circuits. It is also self-limiting information: if a cable is dropping a lot of voltage it is also heating, and a cable sized only by ampacity tables — which protect against overheating — can still be badly undersized for drop on a long run. Both checks are needed; this calculator does the drop check.

Related tools

Figures checked on 24 November 2026. Everything is calculated in your browser — nothing you type is sent anywhere. Design aid only — electrical work must follow your local code.